Connecting the FortiGate-5140 chassis to AC power using the FortiGate-5053 power converter tray

FortiGate-5140-R Chassis Guide

26

01-30000-87705-20090108

http://docs.fortinet.com/

Feedback

Figure 17: Connecting a FortiGate-5140 PEM to a FortiGate-5053 power converter tray

1 Attach the ESD wrist strap to your wrist and to an ESD socket or to a bare metal

surface on the chassis or frame.

2 Loosen the screws and remove the terminal block cover from the FortiGate-5140 PEM.
3 If required, loosen the screws and remove the clear plastic cover from the back of the

FortiGate-5053 power convertor tray.

4 Connect the DC power wires (see

Figure 17

):

• Connect 4 black DC power wires to the FortiGate-5053 power converter tray

V- 48V (BLACK) terminal

• Connect these black wires to connectors 1, 2, 3, and 4 on the FortiGate-5140 PEM

terminal strip labeled -48V/-60 VDC nom.

• Connect 4 red return wires to the FortiGate-5053 power converter tray

V+ RTN (RED) terminal.

• Connect these red wires to connectors 1, 2, 3, and 4 on the FortiGate-5140 PEM

terminal strip labeled RTN.

5 Secure the power wires to the FortiGate-5140 chassis using tie wraps and the back

cable tray.

6 If required, label the black wires -48V.
7 If required, label the red wires RTN.
8 Re-attach the terminal block cover to the FortiGate-5140 PEM.
9 Attach the clear plastic cover to the back of the FortiGate-5053 power converter tray.

1

2

3

4

1

2

3

4

-48V/-60 VDC nom

RETURN

1

2

3

4

1

2

3

4

PEM

V-

V+

100-240VAC 1 2 3

RTN(RED) -48V(BLACK)

RTN (positive)

terminal strip

connectors

1, 2, 3, 4

Red RTN to

FortiGate-5053

RTN (RED)

-48V/-60 VDC

terminal strip

connectors

1, 2, 3, 4

Black -48V/-60 VDC

to FortiGate-5053

-48V(BLACK)

AC in

-48V

-48V

RTN

TERMINAL BLOCK COVER

Remove terminal block cover and

decable before removing PEM.

RTN

V+

(RTN)

(RED)

V-

-48V

(BLACK)