Power connection and configuration

FortiGate-5140-R Chassis Guide
01-30000-87705-20090108

25

http://docs.fortinet.com/

Feedback

Figure 16: Redundant FortiGate-5053 power converter trays and 2 + 1 redundant

FortiGate-5140 power supplies

Connecting a FortiGate-5140 chassis to the FortiGate-5053 power converter tray

To use a FortiGate-5053 power converter tray with the FortiGate-5140 chassis you need
to make DC power connections between the FortiGate-5140 chassis and the FortiGate-
5053 power converter tray. You also need to the connect the FortiGate-5140 chassis to
data center ground.
Each FortiGate-5140 PEM includes 4 connectors that connect power to 4 different power
zones in the FortiGate-5140 chassis. Each power zone supplies power to different
FortiGate-5140 slots and cooling fan trays. You should always connect all 4 power zones.

To connect a FortiGate-5140 PEM to a FortiGate-5053 power converter tray

The following procedure describes how to connect power to PEM A. You can repeat this
procedure to connect PEM B.
You need the following tools and equipment to connect a FortiGate-5140 PEM to a
FortiGate-5053 power converter tray:
• A number 2 Phillips screwdriver.
• An electrostatic discharge (ESD) preventive wrist or ankle strap with connection cord.
• Four black AWG-14 stranded wires with terminal lugs attached and labelled -48V
• Four red AWG-14 stranded wires with terminal lugs attached and labelled RTN
• A FortiGate-5053 power converter tray containing two or three FortiGate-5140 power

supplies and mounted in a rack near the FortiGate-5140 chassis.

Slot 1

Slot 2

Slot 3

2 FortiGate-5053

power convertor trays

1 FortiGate-5140

chassis

2 x 1200W = 2400W

2 + 1 redundancy

2 x 1200W = 2400W

2 + 1 redundancy

6 FortiGate-5140

power supplies

Slot 1

Slot 2

Slot 3

FA N T R AY

FA N T R AY

FA N T R AY

13

11

9

7

5

3

1

2

4

6

8

10

12

14

5140

CR

ITI

CA

L

RE

SE

T

MA

JO

R

MI

NO

R

US

ER

1

US

ER

2

USE

R3

5140SAP

SERIAL 1

SERIAL 2

ALARM

FILTER

1 2

0

1

2

10/100

link/Act

ETH0
Service

RESET

STATUS

Hot Swap

link/Act

ETH0 ETH1

10/100

5000SM

10/100

link/Act

ETH0
Service

RESET

STATUS

Hot Swap

link/Act

ETH0 ETH1

10/100

5000SM

Caution: The FortiGate-5053 power convertor tray should not be connected to AC power
until specified in the following procedure.