Analog input functional block – IDEC SX5L Series User Manual
Page 45

4: S
OFTWARE
S
PECIFICATIONS
4-10
SX5L C
OMMUNICATION
T
ERMINAL
U
SER
’
S
M
ANUAL
Analog Input Functional Block
Analog input channels 0 through 3 correspond to nvoAI0 through nvoAI3, respectively. At the factory settings, analog
input signals of 1 to 5V or 4 to 20 mA are converted to 1 through 100%, and the result is sent to the network.
The output network variable type of the Analog Input functional block can be changed to various SNVTs as shown on
page 4-11.
I/O
Name
Type
Description
Output Network Variable
nvoAI0
SNVT_lev_percent
Corresponds to channel 0
nvoAI1
SNVT_lev_percent
Corresponds to channel 1
nvoAI2
SNVT_lev_percent
Corresponds to channel 2
nvoAI3
SNVT_lev_percent
Corresponds to channel 3
Configuration Property
nciMaxStsSendT1
SCPTmaxSndT
nvoAI0 to nvoAI3 hear tbeat transmission inter val
(factor y setting: 3 minutes)
nciMinSendT1
SCPTminSndT
nvoAI0 to nvoAI3 minimum transmission inter val
(factor y setting: 1 second)
nciMaxRng[0]
SCPTmaxRnge
Designates nvoAI0 maximum value
(factor y setting: 100%)
nciMaxRng[1]
SCPTmaxRnge
Designates nvoAI1 maximum value
(factor y setting: 100%)
nciMaxRng[2]
SCPTmaxRnge
Designates nvoAI2 maximum value
(factor y setting: 100%)
nciMaxRng[3]
SCPTmaxRnge
Designates nvoAI3 maximum value
(factor y setting: 100%)
nciMinRng[0]
SCPTminRnge
Designates nvoAI0 minimum value
(factor y setting: 0%)
nciMinRng[1]
SCPTminRnge
Designates nvoAI1 minimum value
(factor y setting: 0%)
nciMinRng[2]
SCPTminRnge
Designates nvoAI2 minimum value
(factor y setting: 0%)
nciMinRng[3]
SCPTminRnge
Designates nvoAI3 minimum value
(factor y setting: 0%)
nciMinDelta[0]
SCPTsndDelta
Minimum change to send nvoAI0
(factor y setting: 0%)
valid for ever y input level
nciMinDelta[1]
SCPTsndDelta
Minimum change to send nvoAI1
(factor y setting: 0%)
valid for ever y input level
nciMinDelta[2]
SCPTsndDelta
Minimum change to send nvoAI2
(factor y setting: 0%)
valid for ever y input level
nciMinDelta[3]
SCPTsndDelta
Minimum change to send nvoAI3
(factor y setting: 0%)
valid for ever y input level
AI
nvoAI0
nvoAI1
nvoAI2
nvoAI3