Remote-control Relay Control Module SX5L-SBRR081
General Specifications
Remote-control Relay Control Specifications
Rated Power Voltage
24V AC (50/60Hz) supplied from a remote-control transformer
Power Voltage Range
21.6 to 26.4V AC (including 5% ripple)
Power Consumption
1.8 VA (24V AC) not including power consumption by remote-control relays
Power Inrush Current
15A maximum (24V AC)
Allowable Momentary Power Interruption
10 ms minimum (at the rated power voltage)
Dielectric Strength
1,000V AC, 1 minute between power and FG terminals
Insulation Resistance
100 M
Ω minimum between power and FG terminals (500V DC megger)
Operating Temperature
0 to 55°C (no freezing)
Operating Humidity
30 to 90% RH (non-condensing)
Storage Temperature
–20 to +75°C (no freezing)
Storage Humidity
30 to 90% RH (non-condensing)
Pollution Degree
2 (IEC 60664)
Corrosion Immunity
Atmosphere free from corrosive gases
Altitude
Operation: 0 to 2,000m
Transpor t: 0 to 3,000m
Vibration Resistance
10 to 57 Hz amplitude 0.075 mm, 57 to 150 Hz acceleration 9.8 m/s
2
2 hours per axis on each of three mutually perpendicular axes
Shock Resistance
294 m/s
2
, 11-ms sinusoidal half-wave pulse
Mounting
35-mm-wide DIN rail, direct panel mounting (M4 mounting screws)
Weight (approx.)
250g
Input Points
8 points
Input Type
Feedback input from remote control relays through output signal lines
Output Type
Remote-control relay output
Output Pulse ON Width
100 ms
No. of Common Circuits
1 common circuit for 8 points
Applicable
Devices
Remote-control Relay
BR-12D, BR-22D, BR-1 (Mitsubishi Electric)
WR6165 (Matsushita Electric Works)
Remote-control Transformer
BRT-10B, BRT-20B, BRT-1 (Mitsubishi Electric)
WR2301 (Matsushita Electric Works)
Isolation from Power Line
Photocoupler isolation
Dielectric Strength
500V AC, 1 minute between remote-control relay control and FG terminals
Insulation Resistance
100 M
Ω minimum between remote-control relay control and FG terminals
(500V DC megger)