Troubleshooting
9.3
Application errors
Error
Output
Possible cause
Remedy
A warning or
alarm has
occurred.
Depending on the configuration
See table of
error messages
1. See table of error messages
Measured
value (00) is
incorrect
Measured distance
(008) OK?
yes
→
1. Check empty calibr. (005) and
full calibr. (006).
2. Check linearization:
→
level/ullage (040)
→
max. scale (046)
→
diameter vessel (047)
→
Check table
no ↓
Measurement in
bypass or stilling
well?
yes
→
1. Is bypass or stilling well
selected
in tank shape (002)?
2. Is the pipe diameter
(007) correct?
no
↓
Is an
FAR 10 antenna
extension
being used?
yes
→
1. offset (057)
correctly set?
no
↓
An interference
echo
may have been
evaluated.
yes
→
1. Carry out tank mapping
→
basic setup
No change off
measured
value on
filling/empty-
ing
Interference echo
from
installations,
nozzle
or extension on
the
antenna
1. Carry out tank mapping
→
basic setup
2. If necessary, clean antenna
3. If necessary, select better
mounting position
20 mA/100%
F m/ft
E m/ft
4 mA/0%
t
→
D m/ft (008)
actual
expected
20 mA/100%
4 mA/0%
t
→
actual
expected