Commissioning

Radar Tank Gauge

52

Installation and Operations Manual

Function "empty calibr." (005)

This function is used to enter the distance from the flange (reference point of the

measurement) to the minimum level (=zero).

Caution!

For dish bottoms or conical outlets, the zero point should be no lower than the point at

which the radar beam hits the bottom of the tank.

Function "full calibr." (006)

This function is used to enter the distance from the minimum level to the maximum level

(=span).

In principle, it is possible to measure up to the tip of the antenna. However, due to

considerations regarding corrosion and build-up, the end of the measuring range

should not be chosen any closer than 50 mm (2”) to the tip of the antenna.