beautypg.com

G. flue termination – Heat & Glo Fireplace 2197-980 User Manual

Page 42

background image

Heat & Glo • SOHO-N-AUB • 2197-980 Rev. G • 2/13

42

Figure 10.14 Venting through the Wall

• The termination kit should pass through the wall firestops

from the exterior of the building.

• Adjust the termination cap to its final exterior position on

the building and interlock the flue sections.

WARNING! Risk of Fire! the termination cap must be

positioned so that the arrow is pointing up.
• Use a high-temperature sealant gasket to seal between

the pipe and exterior firestop.

EXTERIOR

INTERIOR

Interior

Wall Shield

Inner Flue

Rear Flue

Heat Shield

38 mm min.

overlap

Outer Flue

G. Flue Termination

For Horizontal Terminations using the SLP-TRAP
To attach and secure the termination to the last section of

horizontal flue:
• The rear flue heat shield MUST be placed 1 in. (25 mm)

above the top of the flue between the wall shield and the

base of the termination cap.

• One section of the heat shield is attached to the wall

shield. The other is attached to the termination cap in

the same manner (see Figure 10.14).

• The heat shield sections will overlap to match the wall

thickness (depth).

• If the wall thickness does not allow the required 1-1/2 in. (38

mm) heat shield overlap, an extended heat shield must be

used. The extended heat shield will need to be cut to the

thickness of the wall and be attached to the wall shield.

• The small leg in the shield rests on top of the flue to

properly space it from the pipe section (see Figure 10.14).

Figure 10.15 Termination Cap

1 in. (25 mm)

7-1/2 in.

(192 mm)

MINIMUM

Cap Specification Chart

(depth without using additional pipe sections)

SOHO-N-AUB

SLP-TRAP2

Rear Vent Depth

5-1/2 in. (139 mm) to 9-1/2 in. (241 mm)

SLP-TRAP2 can adjust 4 in. 102 mm (5-3/8 to 9-3/8) (137 mm to 238

mm)