Heat & Glo • SOHO-N-AUB • 2197-980 Rev. G • 2/13

10 in. (254 mm)

10 in. (254 mm)

INTERIOR

WALL SHIELD

F. Install Firestops

For Horizontal Runs - Firestops are REQUIRED on both

sides of a combustible wall through which the flue passes.
To install firestops (heat shield) for horizontal runs that pass

through either interior or exterior walls:
• Cut a 1 in. x 1 in. (25 mm x 25 mm) hole through the wall.
• Position the firestops on both sides of the hole previously

cut and secure the firestops with nails or screws.

• The pipe opening of the firestops

MUST BE placed

towards the bottom of the firestop.

• Continue the flue run through the firestop.

Figure 10.10 Flue Pipe & Firestop

CEILING

NEW

FRAMING

MEMBERS

EXISTING CEILING

JOISTS

CHIMNEY

HOLE

A

B

Figure 10.11 Hole and New Framing Members

For Vertical Runs - One firestop is REQUIRED at the hole

in each ceiling through which the flue passes.
To install firestops for vertical runs that pass through

ceilings:
• Position a plumb bob directly over the center of the

vertical flue component.

• Mark the ceiling to establish the centerpoint of the flue.
• Drill a hole or drive a nail through this center point.
• Check the floor above for any obstructions, such as

wiring or plumbing runs.

• Reposition the fireplace and flue system, if necessary,

to accommodate the ceiling joists and/or obstructions.

• Cut a 9 in. x 9 in. (229 mm x 229 mm) hole through the

ceiling when using SLP pipe. Use the firestop pipe open-

ing as a guide.

• Frame the hole with framing lumber the same size as

the ceiling joists.

A

B

SLP

9 in. (229 mm)

9 in. (229 mm)

Figure 10.12 Ceiling Firestop (Ceiling Side)

Figure 10.13 Attic Firestop

CEILING

CEILING FIRESTOP

RAFTER

NAILS (4 REQUIRED)

JOIST

CEILING FIRESTOP

CEILING

NAILS (4 REQUIRED)

If the area above the ceiling

IS an attic, position and secure

the firestop on top of the previously framed hole.

If the area above the ceiling is

NOT an attic, position

and secure the ceiling firestop on the ceiling side of the

previously cut and framed hole.