16

6

Low Voltage
(92Vac

± 5% or less)

"POWER OK" LED will turn off if voltage
protection operates.
The control voltage safeties automaticlly
reset when voltage is corrected.

7

High Voltage
(147Vac

± 5% or more)

Legend: Comp–compressor; DV–drain valve; FMS–self-contained fan motor; HGV–hot

gas valve; PM–pump motor; TXV–thermostatic expansion valve; WRV–water
regulating valve; WV–inlet water valve

[c] CONTROLS AND ADJUSTMENTS

a) Default Dip Switch Settings

The dip switch is factory-adjusted to the following positions:

S1 Dip Switch No.

1

2

3

4

5

6

7

8

9

10

KM-61BAH

KM-151BAH

OFF OFF

ON

ON

ON

ON

OFF

ON

OFF

ON

KM-101BAH

ON

OFF

ON

ON

ON

ON

OFF

ON

OFF

ON

KM-151BWH

OFF OFF

ON

ON

ON

ON

OFF

ON

ON

OFF

If the S2 dip switch is mounted on the control board, all should be left in the “OFF”
position.

Fig. 1

Freeze Timer (9 & 10)

Water Saver Timer (7 & 8)

Drain Frequency Control (5 & 6)

Drain Timer (3 & 4)

Harvest Timer (1 & 2)

b) Harvest Timer (S1 dip switch 1 & 2)

The harvest timer starts counting when the thermistor reads 48°F (9°C) at the
evaporator outlet.
No adjustment is required under normal use, as the harvest timer is adjusted to the
suitable position. However, a setting longer than the factory setting may be advised in
cases where the fl ush provided at harvest needs to be prolonged for extra cleaning.
Before changing this setting, call the HOSHIZAKI Technical Support Department at