beautypg.com

Output tolerance specifications, Output feature specifications, Battery specifications – HP R5500 User Manual

Page 46: Battery runtime for na/jpn model, Battery runtime for intl model

background image

Specifications 46

Output tolerance specifications

Source of power

Regulation

Utility power (nominal

range)

-10% to +6% of nominal output voltage rating

(within the guidelines of the Computer Business
Equipment Manufacturers Association)

Battery power

±5% of nominal output voltage rating

Output feature specifications

Feature Specification

Online efficiency

94% nominal input voltage

Voltage wave shape

Sine wave; 5% THD with typical PFC load

Surge suppression

High-energy 6500 A peak

Noise filtering

MOVs and line filter for normal and common mode

use

Battery specifications

Feature Specification

Type

Each model contains maintenance-free, sealed, valve

regulated lead-acid batteries with an 8-year minimum float
service life at 25°C (77°F).

Voltage

The battery modules have a battery string voltage of 240

V.

Charging

Complete charge takes no more than 48 hours.

Approximately 3 hours to 80 percent capacity at default
nominal utility voltage and no load.

Battery runtime for NA/JPN model

Load, W (percent)

Estimated battery

runtime (minutes)

Runtime with one ERM

(minutes)

Runtime with two ERMs

(minutes)

20 59

169 303

50 19

61 106

80 9 31 60
100 7 24 46

Battery runtime for INTL model

Load, W (percent)

Estimated battery
runtime (minutes)

Runtime with one ERM
(minutes)

Runtime with two ERMs
(minutes)

20 49

138 247