Battery condition, Bypass is out of range, General alarm condition – HP R5500 User Manual
Page 40: General alarm, Condition, On p, Battery
Troubleshooting 40
Red Off Off Off Off Off On—
Continuous
Yes
Battery condition (on
page
Flashing
red
Off Off Off Flashing
green
Off On—
Continuous
Yes REPO
condition
(on
page
Off Off Off Red Off Off On—1
beep
every 5
seconds
Yes
Site wiring condition
Flashing
red
Off Off Off Off Red On—
Continuous
Yes
UPS power capacity is
exceeded ("
" on page
For the location of individual LEDs, see "UPS front panel LED indicators (on page
Battery condition
Action:
1.
Install the battery module. If the battery module is already installed, remove and reinsert the module.
2.
Allow the UPS batteries to charge for 48 hours.
3.
If the LED does not turn off, replace the batteries ("
UPS battery replacement procedure
4.
If the condition persists, contact an HP authorized service representative.
Bypass is out of range
The input voltage is not within ±12 percent of nominal voltage.
The UPS is receiving utility power that might be unstable or in brownout conditions. The UPS continues to
supply power to the connected equipment. If conditions worsen, the UPS might switch to battery power.
Action:
1.
Check the input voltage and reconfigure the UPS ("
2.
Contact a qualified electrician to verify that the utility power is suitable for the UPS.
General alarm condition
Action:
1.
If power management software is being used, check the log files to obtain specific error information
to help identify the problem.
For more information about the causes of a general alarm condition, see the HP Power Manager
user guide available for download from the HP website (
2.
Check the batteries:
a.
Allow the UPS batteries to charge for 48 hours.
b.
If the Battery Fault LED is red, replace the batteries ("
UPS battery replacement procedure
page
3.
Reduce the load:
a.
" on page