beautypg.com

Vent clearances and framing, A. pipe clearances to combustibles, B. wall penetration framing – Heat & Glo Fireplace VRT-BZ-P-AUB User Manual

Page 37

background image

37

Heat & Glo • VRT-AUB • 2123-980 Rev. J • 2/13

A. Pipe Clearances to Combustibles

WARNING! Risk of Fire! Maintain air space clearance to

vent.

DO NOT pack insulation or other combustibles:

• Between ceiling firestops

• Between wall shield firestops

• Around vent system
Failure to keep insulation or other material away from

vent pipe may cause over heating and fire.

8

Vent Clearances and Framing

Figure 8.2 Wall Penetration

* Shows center of vent framing hole for top or rear venting. The center of

the hole is one 1 in. (25.4 mm) above the center of the horizontal vent

pipe.

* Unit shown with 1-1/2 ft. (457.2 mm) of

vertical pipe. Vertical section will vary by gas.

Refer to vent chart for minimum vertical.

C

D

A*

B*

10 in.

(254 mm)

10 in.

(254 mm)

10 in.

(254 mm)

10 in.

(254 mm)

Figure 8.1 Horizontal Venting Clearances To Combustible

Materials

B. Wall Penetration Framing

Combustible Wall Penetration
Whenever a combustible wall is penetrated, you must

frame a hole for the wall shield firestop(s). The wall shield

firestop maintains minimum clearances and prevents cold

air infiltration.
• The opening must be framed on all four sides using the

same size framing materials as those used in the wall

construction.

• SLP pipe - A wall shield firestop must be placed on each

side of an interior wall. A minimum 1-1/2 inch (38 mm)

overlap of attached heat shields must be maintained.

• See Section 10.H for information for regarding the in-

stallation of a horizontal termination cap.

Non-Combustible Wall Penetration
If the hole being penetrated is surrounded by noncom-

bustible materials such as concrete, a hole with diameter

one inch greater than the pipe is acceptable.
Whenever a non-combustible wall is penetrated, the wall

shield firestop is only required on one side and no heat

shield is necessary.

Note: A 6 in. (152 mm) section of straight flue

must be attached to the fireplace before a 90°

elbow.

A*

B*

C

D

VRT-N-AUB

Inches

69.3 34-3/4 68.3

33-3/4

Millimeters

1761

883

1736

857

VRT-P-AUB

Inches

69.3 34-3/4 68.3

33-3/4

Millimeters

1761

883

1736

857

* When using SLP pipe, minimum clearances from the vent pipe to combustible

materials at inside wall firestops are:

Top: 2-1/2 in. (64 mm)

Bottom: 1/2 in. (13 mm)

Sides: 1 in. (25 mm)

3 in. (76 mm)

top clearance *

1 in. (25 mm)

clearance

bottom & sides

Heat

Shield

Wall

Shield

Firestop

Heat

Shield

WALL

Heat

Shield

Wall

Shield

Firestop

Heat

Shield

WALL

3 in. (76 mm)

top clearance

1 in. (25 mm)

clearance around

vertical sections

Note: Heat shields MUST overlap by a minimum of 1-1/2 in. (38 mm).

• If wall thickness is less than 4 in. (102 mm) the existing heat shields must be field

trimmed.

3 in. (76 mm)

top clearance *

1 in. (25 mm)

clearance

bottom & sides

This manual is related to the following products: