Exhaust Fan Connection Diagram

1

1

2

2

3

3

4

4

D

D

C

C

B

B

A

A

Rev

Size

Drg.

No.

Title

Sheet:

Drawn/
Traced

Engineer
Design

Approved

This Drawing must not be used for Construction

unless signed as approved

7 Columbia Court,

Norwest Business Park
Baulkham Hills NSW 2153

AUSTRALIA

Tel
Fax
Email: [email protected]

A4

No.

Revision - revise on CAD. Do not amend by hand Eng.

App.

Date

Copyright

This document is & shall

remain the property of
Notifier Inertia Fire Systems
Unauthorised use of this
document in any way is
prohibited.

Drawing File No.

C

O

61 2 9894 1444
61 2 9899 4156

=DocumentFullPathAndName

Of:

OFF

AUTO

ON

RUN

STOP

FAULT

+24

0V

START1

STOP1

CONTROL

PCB1128

+24

START

STOP

RUN

STOP

FLT

INDICATION

FAN 1

COMMON +VE

FRONT PANEL CONTROL

FIRE PANEL

FIELD WIRING

START

STOP

* NOTE

THE MECHANICAL SERVICES BOARD

MUST BE CONFIGURED TO HAVE
THE STOP RELAY TO TAKE

PRECEDENCE OVER THE START RELAY

19/8/05

I PERRY

A

EXHAUST FAN (TYPICAL)

2600-EXH

FAN TERMINATION BOARD

AUX +24

AUX 0V

AUX POWER

CONTROL

FAN RUNNING

FAN STOPPED AND POWER AVAILABLE

FAN FAULT OR NO POWER AVAILABLE

R

IB

B

O

N

C

A

B

L

E

1

1

+24

0v

FIRE TRIP

ACF

PCB1125

-

+

IN

OUT

LOAD

-

+

-

+

D1
R1

FROM FIP

RELAY

* NOTE

EITHER THE MAPPING ABOVE MAY

BE USED TO STOP THE EXHAUST FAN

OR THE GENERAL ACF TRIP BELOW,

BUT NOT BOTH.

USE OF THE FIRE TRIP RELAY BELOW

REQUIRES THAT THE MSSB

STOPS THE FAN.

FAN STOP RELAY

(MAPPED TO ACF FOR

GENERAL OR ZONED)