OUTPUT RELAY OPTIONS

Optional Relays can be programmed to simulate: -

Isolate Relay

ACF Output

Brigade Relay #1

Brigade Relay #2

Fault Relay

Mains Fail Relay

General Alarm Relay

Bell Output

Door Holder Relay

Door Switch

Reset

Or Can Be Used To:

"MAP AND"

Up to 5 Zones in Alarm

"MAP OR"

Up to 5 Zones in Alarm

“MAP FAULT”

Up to 5 Zones in Fault

“MAP ISOLATE”

Up to 5 Zones in Isolate

“MAP ISO/FAULT”

Up to 5 Zones in Isolate/Fault

DEFAULT SETTINGS

ACF OUTPUT

NON-LATCHING, NORMALLY DE-ENERGISED

ALARM VERIFICATION (AVF)

3 MINUTES

TIME

1/1/11 11:11

ZONE TYPES

STANDARD LATCH 2S

ZONE OUTPUT CONFIG

I-B-G-A-BR1 & BR2

RELAY MAPPING

MAP -OR-, MAPPING = 1 TO 1
IE: RELAY 1 = ZONE 1, RELAY 2 = ZONE 2.............

The 2600 PANEL is self-configuring on power-up therefore it is not necessary to program the number
of relay boards.
Zone expansion boards fitted must have the correct jumper selected.