IFS-2600 Installation & Programming Manual

Page 45

P/N 10069 ECN08-0066

BATTERY

The 24V batteries are connected at these terminals.

Reverse polarity will cause serious and permanent

damage to the equipment.

DOOR HOLDER AC INPUT

Terminate the door holder AC transformer at these terminals. 24 VAC is the only acceptable power source at
this point. DO NOT connect 240VAC at this point.

OUTPUT RELAYS

STANDBY (N) Normally energised, drops out when power supply (or battery supply) is below specified
voltage.

BRIGADE1

Brigade 1, defaults as energising on any alarm zone, programmable.

BRIGADE2

Brigade 2, defaults as energising on any alarm zone, programmable.

FAULT (N)

Normally energised, drops out on any fault unless that function is isolated.

AC-FAIL (N)

Normally energised, drops out if the mains power is lost.

ISOLATE

Energised if any zone is isolated.

GENERAL1

Energised if any zone goes into alarm

GENERAL2

Energised if any zone goes into alarm