IFS-2600 Installation & Programming Manual
Page 45
P/N 10069 ECN08-0066
BATTERY
The 24V batteries are connected at these terminals.
Reverse polarity will cause serious and permanent
damage to the equipment.
DOOR HOLDER AC INPUT
Terminate the door holder AC transformer at these terminals. 24 VAC is the only acceptable power source at
this point. DO NOT connect 240VAC at this point.
OUTPUT RELAYS
STANDBY (N) Normally energised, drops out when power supply (or battery supply) is below specified
voltage.
BRIGADE1
Brigade 1, defaults as energising on any alarm zone, programmable.
BRIGADE2
Brigade 2, defaults as energising on any alarm zone, programmable.
FAULT (N)
Normally energised, drops out on any fault unless that function is isolated.
AC-FAIL (N)
Normally energised, drops out if the mains power is lost.
ISOLATE
Energised if any zone is isolated.
GENERAL1
Energised if any zone goes into alarm
GENERAL2
Energised if any zone goes into alarm