CONFIGURATION JUMPERS

IFS2004 - JP3 DEFAULT

Holding a short across these pins for 5 seconds during start-up causes the panel to reset to standard
factory defaults. The panel will give 4 beeps after reset, to acknowledge default on start-up.

IFS2004 - JP4 PROGRAM DISABLE

When fitted, jumper between these pins to inhibit program changes.

IFS2004 - JP5 CPU RESET

With panel operating, a momentary short across these pins will cause a CPU restart.

IFS2005 – JP2 DOOR HOLDER BYPASS

If zoned door holder outputs are required and is to be done external to the main termination board,
then the main door holder release needs to be disabled. Fitting a link across JP2 on IFS2005 PCB
does this.

Note: Door holder output is only enabled if optional door holder transformer is fitted. SW1 must be
linked on PCB2004 CPU board prior to Version 6 Firmware.

IFS2006 – JP1 EXTERNAL PS MONITORING

When using external power supply, JP1 link on IFS2006E must be fitted to enable external PSU
monitoring.

IFS804 - JP1-7 ZONE BOARD ADDRESSING

Jumper JP1 to JP7 on zone expansion board IFS-804 selects the addressing for the zones.
Place jumper in link position for the appropriate 8 zones to which the expansion board applies.