Printer output, Cable connection, Programming by computer – Honeywell NOTIFIER IFS-2600 User Manual
Page 17
IFS-2600 Installation & Programming Manual
Page 13
P/N 10069 ECN08-0066
PRINTER OUTPUT
The printer port is designed to be used during testing and commissioning of the panel. The serial printer will
report alarms and faults together with the date and time of the event.
The printer can also be used during
“walk test” mode to produce a history of the test and can also be used to print current programming
configuration.
A DB9 plug male is provided at the top of the main termination board.
This communication port will
communicate with an IBM compatible serial printer (ASCII printer) with the following settings.
Baud Rate
1200 bps
Data Bits
8
Stop Bits
1
Parity
None
Handshaking
DTR
CABLE CONNECTION
Cabling to the printer requires a 4-core telephone style cable with a maximum length of 10 metres. A DB9
socket is required at the panel end.
The printer end is dependent on the type of printer used but is usually a
male DB25. Connection is as follows. A 5-core cable can be used for both comms and printer functions
IFS-2600 END
PRINTER END
DB9 FEMALE
DB25 MALE
DB9 MALE
2
RX (only for programming)
2
3
3
TX
3
2
5
GND
7
5
7
RTS ( do not use)
(5)
(8)
8
CTS ( only for printer)
4
7
PROGRAMMING BY COMPUTER
Programming of the zones, relays, global functions and time can by set with the DOS based program
“2600/SW” using the printer port. (Cannot be used with Windows XP)
After the cable is installed, the program can be run and the menu will prompt for the available functions.
2600