IFS-2600 Installation & Programming Manual

Page 15

P/N 10069 ECN08-0066

ALARM THRESHOLD COMPARATOR TP7

With the panel in the quiescent mode, measure and take note of the INTERNAL 24V DC POWER
SUPPLY as above.

Measure voltage between system 0V and TP7. Adjust multi-turn potentiometer VR4, and adjust until
the voltage is as per the following table.

Rail Voltage

3.3V Setting

Range

20.6

2.833

2.80 to 2.86

21.0

2.888

2.86 to 2.92

21.5

2.956

2.93 to 2.99

22.0

3.025

2.99 to 3.06

22.5

3.094

3.06 to 3.12

23.0

3.163

3.13 to 3.19

23.5

3.231

3.20 to 3.26

24.0

3.300

3.27 to 3.33

24.5

3.369

3.34 to 3.40

25.0

3.438

3.40 to 3.47

25.5

3.506

3.47 to 3.54

26.0

3.575

3.54 to 3.61

26.5

3.644

3.61 to 3.68

27.0

3.713

3.68 to 3.75

27.5

3.781

3.74 to 3.82

27.6

3.795

3.76 to 3.83

28.0

3.850

3.81 to 3.89

FAULT THRESHOLD COMPARATOR TP6

With the panel in the quiescent mode, measure and take note of the INTERNAL 24V DC POWER
SUPPLY as above.

Measure the voltage between system 0V and TP6. Adjust multi-turn potentiometer VR1, and adjust
until the voltage is as per the following table.

Rail Voltage

0.6V Setting

Range

20.6

0.600

0.59 to 0.61

21.0

0.612

0.61 to 0.62

21.5

0.626

0.62 to 0.63

22.0

0.641

0.63 to 0.65

22.5

0.655

0.65 to 0.66

23.0

0.670

0.66 to 0.68

23.5

0.684

0.68 to 0.69

24.0

0.699

0.69 to 0.71

24.5

0.714

0.71 to 0.72

25.0

0.728

0.72 to 0.74

25.5

0.743

0.74 to 0.75

26.0

0.757

0.75 to 0.76

26.5

0.772

0.76 to 0.78

27.0

0.786

0.78 to 0.79

27.5

0.801

0.79 to 0.81

27.6

0.804

0.80 to 0.81

28.0

0.816

0.81 to 0.82