Troubleshooting 88

Battery Test did not run

Possible Cause: The UPS is On Battery.
Action: The UPS must be in a certain state before the battery test runs. For more information, refer to the

section, "Parameters menu option ("

Parameters menu

" on page

51

)."

Browser does not display the web interface for an

installed management module

Action:

1.

Be sure that the IP address and port number are correct. The default port number for non-secure
browser connection is port 80. The default port number for secure SSL browser connection is 443.

2.

Be sure that the web interface (HTTP/HTTPS) is enabled on the management module.

Browser incorrectly displays English or Japanese

characters

Possible Cause: Another user with different language settings logs in to the web interface.
Action: Log out of the web interface, close the browser window, and then sign in to the web interface

again.