XL800 Series Power Consumption
When selecting the appropriate power supply, the power
consumption of the XL800 modules must be taken into
account.
Table 3. XL800 power consumption
max. power consumption
model
24 Vac, 60 Hz
24 Vdc
XCL8010AU with
watchdog load
690 mA
640 mA
XCL8010AU without
watchdog load
190 mA
140 mA
XF821AU, XFL821AU
130 mA
80 mA
XF822AU, XFR822AU,
XFL822AU, XFLR822AU
160 mA
90 mA
XF823AU, XFL823AU
180 mA
130 mA
XF824AU, XFR824AU,
XFL824AU, XFLR824AU
140 mA
90 mA
XFR825AU
140 mA
90 mA
I/O Modules
Variants of I/O Modules
There are two variants of I/O modules:
• Panel Bus I/O modules with communication via Panel Bus
(light-gray housings)
Modules are automatically commissioned (with firmware
download) by the XCL8010AU
• L
ON
W
ORKS
Bus I/O modules (dark-gray housings) with
communication via L
ON
W
ORKS
(FTT10-A, link power
compatible) for easy integration and use with 3
rd
-party
controllers
Terminal Sockets
I/O modules are mounted on the appropriate terminal
sockets. Panel Bus I/O modules and L
ON
W
ORKS
Bus I/O
modules use the same terminal sockets.
Color Coding
To distinguish modules and components, the following color
coding is used:
Table 4. Color coding of Excel 800 Modules
color
part
red
All of the user-accessible adjustable
mechanical parts (i.e., bridge connectors and
locking mechanism) and operating controls
(manual overrides, etc.)
light-gray
Panel Bus I/O modules
dark-gray
L
ON
W
ORKS
Bus I/O modules