Permissible loads – Honeywell XL 800 SERIES User Manual

Page 29

background image

Excel 800

Description of the I/O Modules

29

EN1B-0410GE51

R0908A

Table 34. Description of Relay Output Module terminals

terminal

signal

comment

71, 75

COM a

2-wire communication bus
(LON/Panel Bus)

72, 76

COM b

2-wire communication bus
(LON/Panel Bus)

73, 77

24 V~

Power supply

74, 78

24 V~0

Power supply

11

REL1 N.O.

Relay 1 N.O. contact

12

REL1 N.C.

Relay 1 N.C. contact

13

R1 COM

relay 1 common contact

14

R1 COM

For connection of relay 1 common via
cross connector*

21

REL2 N.O.

Relay 2 N.O. contact

22

REL2 N.C.

Relay 2 N.C. contact

23

R2 COM

Relay 2 common contact

24

R2 COM

For connection of relay 2 common via
cross connector*

31

REL3 N.O.

Relay 3 N.O. contact

32

REL3 N.C.

Relay 3 N.C. contact

33

R3 COM

Relay 3 common contact

RELAY B

L

OCK

1

34

R3 COM

For connection of relay 3 common via
cross connector*

41

REL4 N.O.

Relay 4 N.O. contact

42

REL4 N.C.

Relay 4 N.C. contact

43

R4 COM

Relay 4 common contact

44

R4 COM

For connection of relay 4 common via
cross connector*

51

REL5 N.O.

Relay 5 N.O. contact

52

REL5 N.C.

Relay 5 N.C. contact

53

R5 COM

Relay 5 common contact

54

R5 COM

For connection of relay 5 common via
cross connector*

61

REL6 N.O.

Relay 6 N.O. contact

62

REL6 N.C.

Relay 6 N.C. contact

63

R6 COM

Relay 6 common contact

RELAY B

L

OCK

2

64

R6 COM

For connection of relay 6 common via
cross connector*

25

Shield connection (functional earth),
internally connected to the DIN rail

* Do not connect by wire!

Permissible Loads

Table 35. Permissible loads of Relay Output Modules

max. load

per relay output
module (total)
(common)

24 VAC, 60 Hz
12 A
24 VDC
12 A resistive, 12 A, 0.6 PF

per normally open
contact (common)

24 VAC, 60 Hz
4 A
24 VDC
4 A resistive, 4 A, 0.6 PF

per normally
closed contact
(common)

24 VAC, 2 A, 60 Hz
24 VDC
4 A resistive, 4 A, 0.6 PF

Status LEDs with Manual Overrides

1

2

3

4

5

6

Honeywell

--1

--0
--AUTO

!

Fig. 46. Manual overrides (toggle switches)

The XFR824AU and XFLR824AU Relay Output Modules are
equipped with six manual overrides: one for each relay
output. These toggle switches can manually be set to either
"auto" or "0" or "1".

Table 36. Relay Output Module status LED behavior

mode

LED

N.O.*

(direct)

N.C.*

(reverse)

automatic mode, state
“logical ON”

ON ON

OFF

automatic mode, state
“logical OFF”

OFF OFF

ON

override mode (setting “0”)

flashes

OFF

ON

override mode (setting “1”)

flashes

ON

OFF

*As configured during engineering.