Alarm LED (red)

Table 38. XCL8010AU alarm LED

case

alarm LED

meaning

remedy

1 OFF

Normal operation

No action necessary

2 ON

Watchdog alarm output is powered

– The controller has encountered a

hardware problem
- or -

– The application has a fault

- or -

– The controller has been powered up

without an application or the operator
has manually stopped the application,
e.g., using XL-Online.
In this case, the LED will light up
13 minutes after power-up without
application

Try powering down and then
powering up the XCL8010AU.

If problem persists, check and – if
necessary – reload the application.

If problem still persists, replace
hardware

3 Flashing

Although the controller has encountered a
problem, the watchdog alarm output has not
yet been powered.
If problem persists, the LED will become lit
constantly, see case #2.
The controller performs a warm start.

If it happens only once, the controller
has performed a restart
If, however, it happens multiple times,
then there is an application or hardware
problem (see case #2)

L

ON

W

ORKS

Service LED

Fig. 50. Flashing pattern of the L

ON

W

ORKS

service LED


The L

ON

W

ORKS

service LED of the XCL8010AU Controller Module displays the following flashing patterns indicating possible

failure modes: