C-bus tx and rx leds, Hmi tx and rx leds – Honeywell XL 800 SERIES User Manual
Page 33
Excel 800
Troubleshooting
33
EN1B-0410GE51
R0908A
Table 39. XCL8010AU L
ON
W
ORKS
service LED
case
When can it occur?
meaning
remedy
1
Anytime
Node is configured and running normally
No action necessary
2
Power up of controller
Bad node hardware
►
Replace hardware
3
Power up of controller
Bad node hardware
►
Replace hardware
4
Power up / reset
Node lacks application.
May be caused by neuron chip firmware when
a mismatch occurs on application checksum
►
Using EXCELON, set module to
“configured online”
►
If problem persists, the MIP software
on LW interface has been erased due
to wrong setting performed using
ECHELON tool:
Replace hardware
5
Anytime
Watchdog timer resets occurring.
Possible corrupt EEPROM and bootstrap
mode
►
Download firmware
6
Anytime
Node is unconfigured but has an application
►
Proceed with commissioning
C-Bus Tx and Rx LEDs
Table 40. XCL8010AU C-Bus Tx and Rx LEDs
case
C-Bus LEDs
meaning
remedy
If the C-bus is functioning properly, then the
XCL8010AU is functioning properly
No action necessary
1
Both LEDs are flashing
If the C-bus is not functioning properly, then
the termination can be wrong
►
Check C-bus termination switch S1
(location: see Fig. 4 on page 7)
2
Both LEDs are OFF
No C-bus communication
►
Check C-bus settings
3
Both LEDs are flashing
synchronously
No C-bus communication
►
Check C-bus wiring
HMI Tx and Rx LEDs
Table 41. XCL8010AU HMI Tx and Rx LEDs
case
HMI LEDs
meaning
remedy
1
Both LEDs are flashing
If the HMI Interface is functioning properly,
then the XCL8010AU is functioning properly
No action necessary
2
Both LEDs are OFF
No HMI Interface communication
►
Check HMI Interface connection and
proper earthing of connected
hardware