Description of the I/O Modules

Excel 800

EN1B-0410GE51 R0908A

22

Analog Input Modules

Types of Analog Input Modules

Table 25. Excel 800 Analog Input Modules

type

description

housing

XF821

Panel Bus Analog Input Module light-gray

XFL821

L

ON

W

ORKS

Bus Analog Input

Module

dark-gray

XS821-822 terminal

socket

light-gray

Features

• 8 analog inputs
• Sensor-break and short-circuit detection, see section

"Troubleshooting" on page 31.

Fig. 35. XF821AU Analog Input Module with terminal

socket

Legend
1 Service button S1
2 Hex switch S2
3 Service LED
4 Power LED

Functionality of service LED and power LED: see Table 42
and following.

Terminals

25 26

74

78

73

77

72

76

71

75

24

V~

24

V~

24

V~0

24

V~0

COM

B

COM

B

COM

A

COM

A

AI8

8

AI7

7

AI6

6

AI5

5

AI4

4

AI3

3

AI2

2

AI1

1

18

17

16

15

14

13

12

GND

11

GND GND GND GND GND GND GND

22

V

21

10

GND

9

GND

AUX

V

AUX

Fig. 36. Terminal assignment and internal connections of

Analog Input Modules

Table 26. Description of Analog Input Module terminals

ter-

minal

signal

comment

71, 75

COM a

2-wire communication bus
(LON/Panel Bus)

72, 76

COM b

2-wire communication bus
(LON/Panel Bus)

73, 77

24 V~

Power supply

74, 78

24 V~0

Power supply

1 ─ 8

AI1 ─ AI8 Analog inputs 1 ─ 8

9 ─ 18

GND

Ground. All grounds are connected
internally to each other

21, 22

10 VDC /

5 mA

Auxiliary voltage signal (used e.g. for
supplying setpoint potentiometers).
Connections to these terminals
must be made in the same room.

25, 26

Shield connection (functional earth),
internally connected to the DIN rail


NOTE:

Shield connection to be used for shielded I/O
cables only. It is not allowed to connect a
L

ON

W

ORKS

shield.