Description of the i/o modules, Common features, C-bus termination switch s1 – Honeywell XL 800 SERIES User Manual
Page 21

Excel 800
Description of the I/O Modules
21
EN1B-0410GE51
R0908A
C-Bus Termination Switch S1
The XCL8010AU
Controller Module features a 3-position C-
Bus termination switch S1.
This switch must be set in accordance with the given C-Bus
configuration.
Fig. 34. C-Bus termination switch
Table 21. XCL8010AU
C-Bus termination switch S1
settings
switch setting
S1
baud rate
9.6k all
Up to 9600 baud (default setting)
76k mid
Up to 76800 baud without bus termination
76k end
Up to 76800 baud with bus termination
controller at the end of the C-Bus
Memory
Table 22. XCL8010AU memory
memory
size
usage
SRAM 512
KB
For controller application,
modem trend and firmware
RACL application: 128 KB
Total application: 192 KB
Flash 2
MB
Firmware (1 MB) and application
(1 MB) storage
EPROM
128 KB For bootstrap loader
NOTE: The
XCL8010AU
Controller Module does not
contain a battery. RAM (data and realtime
clocktime) is buffered for 3 days by a super
capacitor.
Description of the I/O Modules
Common Features
Switches Located on the Terminal Socket
Table 23. Terminal socket switches
feature
function
Service button
S1
• LED test, see section "Troubleshooting"
on page 31
• L
ON
W
ORKS
service button functionality
for L
ON
W
ORKS
Bus I/O modules
Hex switch S2
• Module addressing for Panel Bus
I/O modules
LEDs Located on the I/O Module
Table 24. LEDs on I/O module
feature
function
Service LED
(yellow)
• Service information, see section
"Troubleshooting" on page 31
Power LED
(green)
• Information on power supply, see section
"Troubleshooting" on page 31
For the location of these elements, see figures of the
respective modules.