Setting address of panel bus i/o modules, Lonworks bus modules panel bus modules, Xcl8010au – Honeywell XL 800 SERIES User Manual

Page 13: Fig. 12. mixed bus system – correct wiring, Fig. 13. mixed bus system – incorrect wiring

background image

Excel 800

Description of the XCL8010AU Controller Module

13

EN1B-0410GE51

R0908A

71

72

73

74

71

72

73

74

71

72

73

74

11

1

12

2

13

3

14

4

71

72

73

74

75

75

75

76

76

76

77

77

77

78

78

75

76

77

78

78

Panel Bus modules

LonWorks Bus modules

Panel Bus modules

XCL8010AU

Fig. 12. Mixed bus system – correct wiring

71

72

73

74

71

72

73

74

11

1

12

2

13

3

14

4

71

72

73

74

75

75

76

76

77

77

78

75

76

77

78

78

LonWorks Bus modules

Panel Bus modules

XCL8010AU

Fig. 13. Mixed bus system – incorrect wiring

Setting Address of Panel Bus I/O Modules

Each Panel Bus I/O module is assigned its own unique
address. For the sake of clarity for maintenance personnel, it
is recommended that you address the Panel Bus I/O modules
in ascending order 0 through F.

Table 9. HEX switch settings and addresses

HEX switch

0 1 2 3 4 5 6 7

address

01 02 03 04 05 06 07 08

HEX switch

8 9 A B C D E F

address

09 10 11 12 13 14 15 16

Use the rotary HEX switch to set the address to the one
already defined during engineering.