Mounting/Dismounting Modules

Excel 800

EN1B-0410GE51 R0908A

20

Alarm and Power LEDs

The XCL8010AU

Controller Module is equipped with an alarm

LED and a power LED.

Fig. 32. Alarm LED (1) and power LED (2)


Alarm LED (1, red)

Table 17. Controller alarm LED

Off

Normal operation

On

Watchdog alarm output is powered
• The controller has encountered a hardware

problem

• The application has a fault
• The controller has been powered up without

an application or the operator has manually
stopped the application.
In this case, the LED will light up 13 minutes
after power-up without application

Flashing

The watchdog alarm output has not yet been
powered, although the controller has
encountered a problem.
The controller performs a warm start.
If problem persists, the LED will become lit
constantly, see above.
See section "Troubleshooting" on page 31.


Power LED (2, green)

Table 18. Controller power LED

On

Normal operation

Flashing

One or more of the internal voltage supplies
are outside of the permissible ranges.
The controller stops operation.

Check wiring or see section
"Troubleshooting" on page 31.

Goes out
briefly

• The operator has activated the reset

button

• The controller is performing a warm start

Watchdog Status

Table 19. Watchdog status (terminal 4)

status

signal on terminal 4

Failure (= alarm)

24 V

Normal operation

0 V

Modem Interface

NO CONNECTION.

I/O Bus Switch S2

The XCL8010AU

Controller Module features a 2-position I/O

Bus switch S2.
I/O Bus switch S2 must be set in accordance with the kind of
I/O modules connected to communication terminals 71, 72
and 75, 76 of the XCL8010AU Controller Module.
Terminals 71, 72 and 75, 76 must be all connected either to
Panel Bus I/O modules or to L

ON

W

ORKS

Bus I/O modules.

The default setting is Panel.

Fig. 33. I/O Bus switch S2

Table 20. I/O Bus switch settings

communication

S2 setting

L

ON

W

ORKS

Bus only

LON

Panel Bus and L

ON

W

ORKS

Bus

L

ON

W

ORKS

B

US

modules connected to

terminals 11 ─ 14 of the XCL8010AU
Controller Module

Panel

Panel Bus connected to terminals 71, 72 or
75, 76 of the XCL8010AU Controller
Module

Panel