Mounting/Dismounting Modules

Excel 800

EN1B-0410GE51 R0908A

18

Connecting Laptops (XL-Online/CARE)

Connect a laptop (on which e.g., XL-Online or CARE has
been installed) to the HMI interface or L

ON

W

ORKS

interface

of the XCL8010AU

Controller Module by means of

– the XW885 cable or
– the XW585 cable connected with an XW586 Cable.

XCL8010AU Terminals

74

14

10

7

2
3
4

78

73

13

9

6

1

77

72

12

8

5

76

71

11

75

24

V~

24

V~

24

V~

24

V~0

LON

2

C-

C-

C+

C+

LON

2

LON

1

LON

1

24

V~0

24

V~0

NC

24

V~0

COM

B

COM

B

COM

A

COM

A

SHIELD

SHIELD

8 7 65 4 3 21

*

*Watch Dog

Relay

Fig. 26. Terminal assignment and internal connections of

the XCL8010AU

Controller Module

Table 12. Description of XCL8010AU terminals

ter-

minal

signal

comment

71, 75 COM a

2-wire communication bus
(LON/Panel Bus)

72, 76 COM b

2-wire communication bus
(LON/Panel Bus)

73, 77

24 V~ Power supply for I/O modules

74, 78 24 V~0 Power supply for I/O modules

1

24 V~ Power supply from transformer

2

24 V~0 Power supply from transformer

3

24 V~0 Alarm/watchdog output

4 NC

Alarm/watchdog

output

5, 8

C+

C-Bus

6, 9

C-

C-Bus

7, 10

Shield C-Bus shield

11, 12

LON

L

ON

W

ORKS

IN

13, 14

LON

L

ON

W

ORKS

OUT

Features

L

ON

W

ORKS

Interface and Terminals

The XCL8010AU

Controller Module features

• An RJ45 socket serving as an interface

to connect laptops or HMIs to the L

ON

W

ORKS

Bus

• L

ON

W

ORKS

terminals 11, 12, 13, and 14

to connect L

ON

W

ORKS

Bus I/O modules or other

L

ON

W

ORKS

devices to the XCL8010AU Controller or other

L

ON

W

ORKS

controllers.

Fig. 27. L

ON

W

ORKS

interface and L

ON

W

ORKS

terminals


L

ON

W

ORKS

Interface Signals on RJ45 Socket

Table 13. Signals of L

ON

W

ORKS

interface

pin

signal type

1

Connection to L

ON

W

ORKS

Bus

2

Connection to L

ON

W

ORKS

Bus

3 ─ 8

Not used

L

ON

W

ORKS

Service LED and Button

The XCL8010AU

Controller Module is equipped with a

L

ON

W

ORKS

service button and corresponding L

ON

W

ORKS

Service LED (status: yellow/OFF).

1

LON

2

Fig. 28. L

ON

W

ORKS

service button (1) and service LED (2)