INSTALLATION
Locating Built-in Clearances
Insulated jacket
If the grill is to be placed into a combustible enclosure, an approved insulated jacket is necessary.
Insulated jackets are available from your dealer. Use only the DCS insulated jacket which has
specifically been designed and tested for this purpose. Review the detail drawing shown (Fig. 06)
and take into account the provisions shown for gas line hook-up clearance in the right rear corner.
It is required that ventilation holes are provided in the enclosure to eliminate the potential build-up
of gas in the event of a gas leak. The supporting ledges or deck must be level and flat and strong
enough to support the grill and insulated jacket. The counter should also be level.
IMPORTANT!
Installing this product into a combustible enclosure without an insulated jacket could result in fire,
property damage and personal injury.
A
A
A
FIG. 03
**DEFINITION OF COMBUSTIBLE MATERIAL
- Any materials of a building structure or decorative
structure made of wood, compressed paper, plant fibers, vinyl/plastic or other materials that
are capable of transferring heat or being ignited and burned. Such material shall be considered
combustible even though flame-proofed, fire-retardant treated or surface-painted, or plastered.
IMPORTANT!
It is required that a minimum of three 10x10" (645 x 645mm) of ventilation opening be provided for
both the left and right sides, as well as the back of enclosure (Fig. 05), in order to safely dissipate
unburned gas vapors in the event of a gas supply leak.
Clearances to combustible construction**
Minimum of 18” (457mm) from the sides and rear of grill must be maintained to adjacent vertical
combustible construction, above the counter top level. Intense heat, and large volumes of smoke will
exhaust from the rear of the grill (Fig. 01b). This may discolor or damage unprotected areas. Do not
install under unprotected combustible construction without using a fire safe ventilation system.
A 18” (457mm) minimum clearance must be maintained under the counter top to combustible con-
struction. The clearance can be modified by a use of an insulated jacket. Insulated jackets can be
purchased from our website, www.dcsappliances.com.
PRODUCT DIMENSIONS
INCHES (MM)
A
Minimum distance from combustible surface to grill
18" (457)
COMBUSTIBLE
SURFACE
=
EN