General specifications, Hardware specifications – ProSoft Technology MVI46-DNP User Manual
Page 57

Reference MVI46-DNP
♦ SLC Platform
Master/Slave Communication Module
ProSoft Technology, Inc.
Page 57 of 143
August 23, 2007
Support for the storage and transfer of all DNP data types across the
backplane
Communication
parameters
o
Address: 0 to 65534 (slave mode)
o
Baud rate: 110 to 115K
o
Parity: none, data bits: 8, Stop bit: 1
o
RTS on delay: 0 to 65535 milliseconds
o
RTS off delay: 0 to 65535 milliseconds
DNP protocol specifications
o
DNP 3.0 slave level 2 minimum
o
DNP 3.0 master level 2 minimum
Unsolicited responses supported on slave ports
5.1.2 General
Specifications
Single Slot – 1746 backplane compatible (Local or extended I/O rack only.
Remote rack not supported)
The module is recognized as an Input/Output module and has access to
processor memory for data transfer between processor and module using
M0/M1 files
Ladder Logic is used for data transfer between module and processor.
Sample ladder file included
Configuration data obtained from configuration text file downloaded to
module. Sample configuration file included
5.1.3 Hardware
Specifications
Specification
Description
Backplane Current Load
800 ma @ 5V (from backplane)
Operating Temperature
0 to 60°C (32 to 140°F)
Storage Temperature
–40 to 85°C (–40 to 185°F)
Shock
30g operational, 50g non-operational
Relative Humidity
5% to 95% (non-condensing)
Vibration
5 g from 10150 Hz
Processor
Compatible with Rockwell Automation SLC 5/02 M0/M1
capable processors or newer
LED indicators
Module status, Backplane transfer status, Application
status, Serial activity and error LED status
Debug/Configuration port (CFG)
CFG Port (CFG)
RJ45 (DB-9M with supplied cable)
RS-232 only
Configuration Connector
RJ45 RS-232 Connector (RJ45 to DB-9 cable shipped
with unit)
Application Ports
Application Serial port (PRT1, PRT2)
(Serial Modules)
Two RJ45 RS-232/422/485 Application ports