Binary output command examples – ProSoft Technology MVI46-DNP User Manual
Page 24

MVI46-DNP ♦ SLC Platform
Configuring the Module
Master/Slave Communication Module
Page 24 of 143
ProSoft Technology, Inc.
August 23, 2007
Port/Flg
Slave
Object
Var
Func
Addr Pnt Cnt DNP DB IED DB Poll Int
WORD
0
1
2
3
4
5
6
7
8
9
VALUE
14
15
1
0
1
0
-32
200
0
2
DNP BI's
IED #15
Address
Address
200
0
231
31
IED BI's
Address
0
NOTE:
Data accessible by remote
DNP master and PLC. Events for
points generated by module. All IED
31
generated events are ignored.
Command for Port 2, Enabled, RBE Flag Set.
IED Unit 15 is to be polled.
Object type is 1 (Binary Input).
Variation of 0 (default variation).
Function 1 is for a read.
Slave address ignored (Qual 6, all points).
Point count of -32 indicates only first 32 points are to
be used.
DNP DB address of 200 is where first data point is
placed.
IED DB address of 0 is where first data point is
placed.
Poll command every 2-seconds.
BINARY OUTPUT COMMAND EXAMPLES:
Port/Flg
Slave
Object
Var
Func
Addr Pnt Cnt DNP DB IED DB Poll Int
WORD
0
1
2
3
4
5
6
7
8
9
VALUE
14
15
12
1
5
10
2
200
0
0
IED #15
DNP BO's
Address
Address
10
200
11
201
Command for Port 2, Enabled, only operate on
point change & use DNP Database.
IED Unit 15 is to be polled.
Object type is 12 (Binary Output Control).
Variation of 1 (Control Relay Output Block).
Function 5 is for direct operate.
Slave address of 10 is starting point in IED.
Two points are to be transferred.
DNP DB address of 200 is first source point.
IED DB is not used.
Command not a polled command.
Port/Flg
Slave
Object
Var
Func
Addr Pnt Cnt DNP DB IED DB Poll Int
WORD
0
1
2
3
4
5
6
7
8
9
VALUE
30
15
12
1
5
10
1
0
25
0
IED #15
IED BO's
Address
Address
10
25
Command for Port 2, Enabled, only operate on
point change & use IED Database.
IED Unit 15 is to be polled.
Object type is 12 (Binary Output Control).
Variation of 1 (Control Relay Output Block).
Function 5 is for direct operate.
Slave address of 10 is starting point in IED.
One point is transferred.
DNP DB is not used.
IED DB address of 25 is first source point.
Command not a polled command.