ProSoft Technology MVI46-DNP User Manual
Page 115

Reference MVI46-DNP
♦ SLC Platform
Master/Slave Communication Module
ProSoft Technology, Inc.
Page 115 of 143
August 23, 2007
Object
Request
Response
Obj Var Description
Func
Codes
Qual
Codes
(hex)
Func
Codes
Qual
Codes
(hex)
Data
Size
(bits)
Notes
8
16-Bit Frozen
Delta Counter
With Time Of
Freeze
72
Slave will return
Unknown Object to
this request
9
32-Bit Frozen
Counter Without
Flag
1
06
129, 130
00, 01
32
Slave will return this
variation
10
16-Bit Frozen
Counter Without
Flag
1
06
129, 130
00, 01
16
Slave will return this
variation (counter
upper 16-bits
removed)
11
32-Bit Frozen
Delta Counter
Without Flag
32
Slave will return
Unknown Object to
this request
12
16-Bit Frozen
Delta Counter
Without Flag
16
Slave will return
Unknown Object to
this request
22 0 Counter
Change
Event - All
Variations
1 06,
07,
08
Slave will parse this
request and return
no data
1
32-Bit Counter
Change Event
Without Time
129, 130
17, 28
40
Slave will return
Unknown Object to
this request
2
16-Bit Counter
Change Event
Without Time
129, 130
17, 28
24
Slave will return
Unknown Object to
this request
3
32-Bit Delta
Counter Change
Event Without
Time
40
Slave will return
Unknown Object to
this request
4
16-Bit Delta
Counter Change
Event Without
Time
24
Slave will return
Unknown Object to
this request
5
32-Bit Counter
Change Event
With Time
88
Slave will return
Unknown Object to
this request
6
16-Bit Counter
Change Event
With Time
72
Slave will return
Unknown Object to
this request
7
32-Bit Delta
Counter Change
Event With Time
88
Slave will return
Unknown Object to
this request
8
16-Bit Delta
Counter Change
Event With Time
72
Slave will return
Unknown Object to
this request
23 0 Frozen
Counter
Event - All
Variations
Slave will return
Unknown Object to
this request