ProSoft Technology MVI46-DNP User Manual
Page 123

Reference MVI46-DNP
♦ SLC Platform
Master/Slave Communication Module
ProSoft Technology, Inc.
Page 123 of 143
August 23, 2007
Object
Request
Response
Obj Var Description
Func
Codes
Qual
Codes
(hex)
Func
Codes
Qual
Codes
(hex)
Data
Size
(bits)
Notes
22 0 Counter
Change
Event - All
Variations
1 06,
07,
08
Master will not
generate a
request for this
variation.
1
32-Bit Counter
Change Event
Without Time
129, 130
17, 28
40
Master will
process this
variation.
2
16-Bit Counter
Change Event
Without Time
129, 130
17, 28
24
Master will
process this
variation.
3
32-Bit Delta Counter
Change Event
Without Time
40
4
16-Bit Delta Counter
Change Event
Without Time
24
5
32-Bit Counter
Change Event With
Time
88
6
16-Bit Counter
Change Event With
Time
72
7
32-Bit Delta Counter
Change Event With
Time
88
8
16-Bit Delta Counter
Change Event With
Time
72
23 0 Frozen
Counter
Event - All
Variations
1
32-Bit Frozen
Counter Event
Without Time
40
2
16-Bit Frozen
Counter Event
Without Time
24
3
32-Bit Frozen Delta
Counter Event
Without Time
40
4
16-Bit Frozen Delta
Counter Event
Without Time
24
5
32-Bit Frozen
Counter Event With
Time
88
6
16-Bit Frozen
Counter Event With
Time
72