ProSoft Technology MVI46-DNP User Manual
Page 124

MVI46-DNP ♦ SLC Platform
Reference
Master/Slave Communication Module
Page 124 of 143
ProSoft Technology, Inc.
August 23, 2007
Object
Request
Response
Obj Var Description
Func
Codes
Qual
Codes
(hex)
Func
Codes
Qual
Codes
(hex)
Data
Size
(bits)
Notes
7
32-Bit Frozen Delta
Counter Event With
Time
88
8
16-Bit Frozen Delta
Counter Event With
Time
72
30
0
Analog Input - All
Variations
1
06
16
Master will
generate this
variation.
1
32-Bit Analog Input
1
06
129, 130
00, 01
40
Master will
generate this
variation. Note:
Data returned
will only be
Least
Significant 16
bits from Slave
2
16-Bit Analog Input
1
06
129, 130
00, 01
24
Master will
generate and
process this
variation.
3
32-Bit Analog Input
Without Flag
1
06
129, 130
00, 01
32
Master will
generate this
variation. Note:
Data returned
will only be
Least
Significant 16
bits from Slave
4
16-Bit Analog Input
Without Flag
1
06
129, 130
00, 01
16
Master will
generate and
process this
variation.
31
0
Frozen Analog Input
- All Variations
1
32-Bit Frozen
Analog Input
40
2
16-Bit Frozen
Analog Input
24
3
32-Bit Frozen
Analog Input With
Time To Freeze
88
4
16-Bit Frozen
Analog Input With
Time To Freeze
72
5
32-Bit Frozen
Analog Input
Without Flag
32