Dnp configuration forms, Mvi46-dnp communication module configuration, Configuration forms – ProSoft Technology MVI46-DNP User Manual
Page 101

Reference MVI46-DNP
♦ SLC Platform
Master/Slave Communication Module
ProSoft Technology, Inc.
Page 101 of 143
August 23, 2007
Error Code
Name
Description
1004
Response to select before operate does not
match
The select response message received from the slave
module is not that expected from the last select
request. This indicates a synchronization problem
between the master and slave devices.
1005
Response does not contain date/time object
The response message from the slave device does not
contain a date/time object. The master expects this
object for the response message.
1006
Time-out condition on response
The slave device did not respond to the last request
message from the master within the time-out set for the
IED device. The application layer time-out value is
specified for each IED unit in the slave configuration
table in the module. This table is established each time
the module performs the restart operation.
1007
Function code in application layer message not
supported
The function code returned in the response message is
not valid for the application layer or not supported by
the module.
1008
Read operation not supported for
object/variation
The application layer response message contains an
object that does not support the read function.
1009
Operate function not supported for the
object/variation
The application layer response message contains an
object that does not support the operate function.
1010
Write operation not supported for the
object/variation
The application layer response message contains an
object that does not support the write function.
5.7
DNP Configuration Forms
This section contains a configuration form to be used when designing an
application.
5.7.1 MVI46-DNP
Communication Module Configuration
[Section]/Item Value
Range
Description
[MODULE]
General module configuration section
Module Name:
0 to 80 characters This parameter assigns a name to the module that can
be viewed using the configuration/debug port. Use this
parameter to identify the module and the configuration
file.
[Section]/Item Value
Range
Description
[DNP Slave]
DNP Slave configuration information
Internal Slave ID:
0 to 65534
This is the DNP address for the module. All messages
with this address from the master will be processed by
the module.
Baud Rate:
Baud rate value Primary DNP Port Baud Rate: 300, 600, 1200, 2400,
4800, 9600, 19200, 384 (38400) , 576 (57600), 115
(115200)
RTS On:
0 to 65535
milliseconds
This value represents the number of 1 ms increments to
be inserted between asserting the RTS modem line and
the actual transmission of the data.