Object
Request
Response
Obj Var Description
Func
Codes
Qual
Codes
(hex)
Func
Codes
Qual
Codes
(hex)
Data
Size
(bits)
Notes
6
16-Bit Frozen
Analog Input
Without Flag
16
32 0 Analog
Change
Event - All
Variations
1 06,
07,
08
24
Master will
generate this
variation
1
32-Bit Analog
Change Event
Without Time
1
06, 07,
08
129, 130
17, 28
40
Master will
generate and
process this
variation.
2
16-Bit Analog
Change Event
Without Time
1
06, 07,
08
129, 130
17, 28
24
Master will
generate and
process this
variation.
3
32-Bit Analog
Change Event With
Time
1
06, 07,
08
129, 130
17, 28
88
Master will
generate and
process this
variation.
4
16-Bit Analog
Change Event With
Time
1
06, 07,
08
129, 130
17, 28
72
Master will
generate and
process this
variation.
33 0 Frozen
Analog
Event - All
Variations
1
32-Bit Frozen
Analog Event
Without Time
40
2
16-Bit Frozen
Analog Event
Without Time
24
3
32-Bit Frozen
Analog Event With
Time
88
4
16-Bit Frozen
Analog Event With
Time
72
40 0 Analog
Output
Status - All
Variations
1
06
24
1
32-Bit Analog
Output Status
40
2
16-Bit Analog
Output Status
129, 130
00, 01
24
Master does not
use this object
type and will not
generate a
message or
process this
type.
41
0
Analog Output Block
- All Variations
24
1
32-Bit Analog
Output Block
40