beautypg.com

ProSoft Technology MVI56-GEC User Manual

Page 72

background image

Reference

MVI56-GEC ♦ ControlLogix Platform

User Manual

Generic ASCII Ethernet Communication Module

Page 72 of 108

ProSoft Technology, Inc.

October 8, 2010

Backplane Data Transfer
The MVI56-GEC module communicates directly over the ControlLogix

backplane. Data travels between the module and the ControlLogix processor

across the backplane using the module's input and output images. The update

frequency of the data is determined by the user-defined scan rate for the module,

and the communication load on the module. Typical updates are in the range of 1

to 10 milliseconds.
Data received by the module's clients and servers is placed in the module's

Database. This data is read and then processed by the ladder logic in the

ControlLogix processor through the Input Image (Local Input connection). The

input image parameter in RSLogix 5000 for the module is set to 250 registers

(500 bytes).

The processor writes data through the Output Image (Local Output connection)

for transfer into the module's Database. The module's program extracts the data

from the module's Database and transmits the data out to the Ethernet network.

Each message is directed to a client or server that is connected to a remote host.

The Output image parameter in RSLogix for the module is set to 248 registers

(496 bytes). This large I/O area permits fast throughput of data between the

module and the processor.
The following illustration shows the data transfer method used to move data

between the ControlLogix processor, the MVI56-GEC module, and the Ethernet

network.

All data transferred between the module and the processor over the backplane is

through the input and output images. Ladder logic must be written in the

ControlLogix processor to interface the input and output image data defined in

the controller tags.
You must configure the module properly for accurate reception of data through its

ports, and you must program the ladder logic to interpret the data from the

module and send the correct response to the module.
Use the sample ladder logic program on the CD-ROM to establish data transfer

between the module and the processor.