MVI56-GEC ♦ ControlLogix Platform

Diagnostics and Troubleshooting

Generic ASCII Ethernet Communication Module

User Manual

ProSoft Technology, Inc.

Page 61 of 108

October 8, 2010

Transferring the Configuration File from the PC to the Module
On the Diagnostics Menu this is referred to as Receive Module Configuration.
Press [R]

to receive (download) the configuration file from your PC to the module

and store the file on the module’s Compact Flash Card (Personality Module) or

Flash RAM.
Press [Y]

to confirm the file transfer, and then follow the instructions on the

terminal screen to complete the file transfer process.
After the file has been successfully downloaded, the module will restart the

program and load the new configuration information. Review the new

configuration using menu commands [6]

and [0]

to verify that the module is

configured correctly.

Transferring the Configuration File from The Module to the PC
On the Diagnostics Menu this is referred to as Send Module Configuration.
Press [S]

to send (upload) the configuration file from the module to your PC.

Press [Y]

to confirm the file transfer, and then follow the instructions on the

terminal screen to complete the file transfer process.
After the file has been successfully uploaded, you can open and edit the file to

change the module’s configuration.

Resetting Diagnostic Data
Press [U]

to reset the status counters for the Client and/or servers in the module.

Viewing Version Information
Press [V]

to view version information for the module.

Use this command to view the current version of the software for the module, as

well as other important values. You may be asked to provide this information

when calling for technical support on the product.
Values at the bottom of the display are important in determining module

operation. The Program Scan Counter value is incremented each time a

module’s program cycle is complete.

Tip: Repeat this command at one-second intervals to determine the frequency of program
execution.

Warm Booting the Module
Press [W]

from the Main menu to warm boot (restart) the module.

This command will cause the program to exit and reload, refreshing configuration

parameters that must be set on program initialization. Only use this command if

you must force the module to reboot.