ProSoft Technology MVI56-GEC User Manual

Page 31

background image

MVI56-GEC ♦ ControlLogix Platform

Configuring the MVI56-GEC Module

Generic ASCII Ethernet Communication Module

User Manual

ProSoft Technology, Inc.

Page 31 of 108

October 8, 2010

2.3

[Server x]

You can configure up to five servers ([Server 0] through [Server 4]). The

configuration section for each server contains the same set of parameters. You

can configure the parameters for each server to meet the requirements of your

application.

2.3.1 Enabled

Yes or No
This parameter determines if the server will be utilized by the module. If a value

of "Yes" is entered, the server will be used. Any other value will disable the

server.

2.3.2 Service Port Number

1 to 65535
This parameter sets the TCP/IP service port for this server. Each server can

have its own unique service port or can share the same number with other

servers.

2.3.3 Connection Timeout

0 or 5000 to 65535
This parameter specifies the number of milliseconds the server will permit the

server to be inactive after a connection is made before closing the socket. This

timeout period is reset on each read or write packet. If the parameter is set to 0,

the connection will not timeout.

2.3.4 Connection Close Type

0, 1 or 2
This coded parameter defines the personality of the server after a connection is

made. If the parameter is set to 0, the socket will only be closed when a request

from the client is received or the connection timeout is exceeded. If a value of 1

is selected, the server will close the socket after it transmits a single message. If

a value of 2 is selected, the server will close the socket after it receives a

message.

2.3.5 Swap Rx Data Bytes

Yes or No
This parameter determines if the data received by the server will have the byte

order of the data swapped. If the parameter is set to No, no byte swapping will

occur. If the parameter is set to Yes, the odd byte will be swapped with the even

byte in each word of data received.