Master mode operation – ProSoft Technology CLX-APACS User Manual
Page 33

QTS-CLX-APACS Page
27
Master Mode Operation
WARNING!
Never connect the APACS in master mode to the network while the
ACM is controlling I/O. It transmits even if there is no configuration
and will disrupt communication.
The following is a short summary of the steps typically followed. Refer to the
appropriate manual section for details.
Step Operation
See page
1
Install the QTS-CLX-APACS module in the
ControlLogix chassis
2
Power down all APACS racks.
3
Connect the module to the APACS IOBUS
4
Run the QTS-CLX-MAS master configuration
program, ClxApacsMasCfg.exe
5
Temporarily load the monitor firmware on the
QTS-CLX-APACS
6
Clear the stored ACM configuration on the
QTS-CLX-APACS
7
Power up the APACS racks and wait for the OK
LEDs on all modules to be green
8
Read the captured configuration data that the ACM
sent to the modules
9
Check that all modules and channels are correct
10
Assign ControlLogix addresses to the IOBUS data
11
Set the module name
12
Save the configuration
13
Remove the ACM
14
Change the QTS-CLX-APACS to master mode
15
Download the configuration to the module
16
Configure the module in RSLogix 5000
17
Create aliases for RSLogix 5000
18
Import the aliases into RSLogix 5000
19
Use the aliases to access the data