Auto-Polling
This feature is enabled by setting the AUTO-POLL CODE (in the configuration
file) to a value of P (point-to-point). If the value N is entered for the parameter,
the auto-poll feature is disabled. When the feature is disabled, the channel will
only execute the commands enabled in the user command list. When the auto-
polling mode is enabled, the module will automatically acquire data from the
HART instruments attached to a channel without the use of user commands. If
user commands are present and enabled when the feature is enabled, they will
also be executed independent of auto-polling.
With the auto-poll feature enabled, the module automatically generates the
following HART commands and stores the data in the module's database at the
user-specified location:
CMD
Description
0
Read Unique Identifier
3
Read Current and Four Dynamic Variables
13
Read Tag, Descriptor and Date
14
Read PV Sensor Information
15
Read Output Information
If the unit is set for point-to-point mode, the module will automatically gather the
information for the device with the polling address (short address) of zero and
place the data into the database. Each device requires a 50-word database area
with the format shown in the following table.
DB Byte
Offset
Type
Description
Byte
Cnt
Data
Source
Use of Data
0
byte
Auto-polling command status bits
1
App
Status
1
byte
Last first status byte received from
device
1
Resp
Status
2
byte
Last second status byte received
from device
1
Resp
Status
3
byte
Manufacture ID Code
1
CMD 0
LongAddress
4
byte
Device Type Code
1
CMD 0
LongAddress
5
byte
Minimum number of preambles
1
CMD 0
Msgconstruction
6
byte
Universal Command Major Rev #
1
CMD 0
Msgchoice
7
byte
Device Revision Level
1
CMD 0
Info
8
byte
Software Revision Level
1
CMD 0
Info
9
byte
Hardware Revision Level/Physical
Signaling Code
1
CMD 0
Info
10
byte
Device Flags
1
CMD 0
Info
11 to 13
byte
Device ID
3
CMD 0
Long Address
14
byte
Minimum number of preambles to
be sent with the response message
from the slave to the master.
1
CMD 0
15
byte
Maximum number of device
variables
1
CMD 0
Info
16 to 17
word
Configuration Change Counter
2
CMD 0
Info