Reference

MVI69-HART ♦ CompactLogix Platform

User Manual

HART Multi-drop Master Communication Module

Page 98 of 169

ProSoft Technology, Inc.

March 29, 2012

Auto-Polling
This feature is enabled by setting the AUTO-POLL CODE (in the configuration

file) to a value of P (point-to-point). If the value N is entered for the parameter,

the auto-poll feature is disabled. When the feature is disabled, the channel will

only execute the commands enabled in the user command list. When the auto-

polling mode is enabled, the module will automatically acquire data from the

HART instruments attached to a channel without the use of user commands. If

user commands are present and enabled when the feature is enabled, they will

also be executed independent of auto-polling.
With the auto-poll feature enabled, the module automatically generates the

following HART commands and stores the data in the module's database at the

user-specified location:

CMD

Description

0

Read Unique Identifier

3

Read Current and Four Dynamic Variables

13

Read Tag, Descriptor and Date

14

Read PV Sensor Information

15

Read Output Information

If the unit is set for point-to-point mode, the module will automatically gather the

information for the device with the polling address (short address) of zero and

place the data into the database. Each device requires a 50-word database area

with the format shown in the following table.

DB Byte
Offset

Type

Description

Byte
Cnt

Data
Source

Use of Data

0

byte

Auto-polling command status bits

1

App

Status

1

byte

Last first status byte received from

device

1

Resp

Status

2

byte

Last second status byte received

from device

1

Resp

Status

3

byte

Manufacture ID Code

1

CMD 0

LongAddress

4

byte

Device Type Code

1

CMD 0

LongAddress

5

byte

Minimum number of preambles

1

CMD 0

Msgconstruction

6

byte

Universal Command Major Rev #

1

CMD 0

Msgchoice

7

byte

Device Revision Level

1

CMD 0

Info

8

byte

Software Revision Level

1

CMD 0

Info

9

byte

Hardware Revision Level/Physical

Signaling Code

1

CMD 0

Info

10

byte

Device Flags

1

CMD 0

Info

11 to 13

byte

Device ID

3

CMD 0

Long Address

14

byte

Minimum number of preambles to
be sent with the response message

from the slave to the master.

1

CMD 0

15

byte

Maximum number of device

variables

1

CMD 0

Info

16 to 17

word

Configuration Change Counter

2

CMD 0

Info