Diagnostics and Troubleshooting
MVI69-HART ♦ CompactLogix Platform
User Manual
HART Multi-drop Master Communication Module
Page 70 of 169
ProSoft Technology, Inc.
March 29, 2012
Opening the Data Analyzer Menu
Press [A]
to open the Data Analyzer Menu. Use this command to view all bytes
of data transferred on each port. Both the transmitted and received data bytes
are displayed. Refer to Data Analyzer (page 74) for more information about this
menu.
Important: When in analyzer mode, program execution will slow down. Only use this tool during a
troubleshooting session. Before disconnecting from the Config/Debug port, please press [S]
to stop
the data analyzer, and then press [M]
to return to the main menu. This action will allow the module
to resume its normal high speed operating mode.
Viewing the Slave Status List
Press [V] to view the slave status values associated with the ports. The slave
status values are defined as follows:
ERR = Device in Error
OK = Device OK
[Blank] = Device Not Polled.
Opening the Command Error List Menu
Press [E]
(port 1) or [F]
(port 2) to open the Command Error List. This list
consists of multiple pages of command list error/status data. Press [?]
to view a
list of commands available on this menu.
Opening the Command List Menu
Press [E] (port 1) or [F] (port 2) to open the Command List menu. Use this
command to view the configured command list for the module.
Viewing the Master Command List Help
Press [H] to view a help screen with explanations of each item that appears on
the command list.