Reference
MVI69-HART ♦ CompactLogix Platform
User Manual
HART Multi-drop Master Communication Module
Page 120 of 169
ProSoft Technology, Inc.
March 29, 2012
COMMAND 12 - Read Message
Description
This command reads an ASCII message contained in the HART Device and
written by the Write Message command 17.
Write Parameters
NONE
Floating Point Data Returned
NONE
Integer Data Returned
Word
High Byte
Low Byte
0
STATUS WORD
1
Message ASCII Character 0
Message ASCII Character 1
2
Message ASCII Character 2
Message ASCII Character 3
.
.
.
.
.
.
14
Message ASCII Character 28
Message ASCII Character 29
15
Message ASCII Character 30
Message ASCII Character 31