beautypg.com

ProSoft Technology MVI69-HART User Manual

Page 43

background image

MVI69-HART ♦ CompactLogix Platform

Module Configuration

HART Multi-drop Master Communication Module

User Manual

ProSoft Technology, Inc.

Page 43 of 169

March 29, 2012

The user can configure the command parameters as described in the following

table in order to correctly read the command 3 results to the module database:

Index

Parameter

Value

Observation

1

Enable

1

The command is sent continuously

2

Float DB

Address

240

The floating point results will be copied to the internal
database starting at word-address 240 (from 240 to

249)

3

Poll Interval

0

The command is sent without any delay

4

Word Count

10

The command returns 10 words of floating point data

5

Swap Code

3

The bytes in each returned floating point word are

swapped

6

Short

Address

0

This command is sent to the Hart slave device
using short address 0

7

Function

Code

3

The command function 3 (READ DYNAMIC

VARIABLES) is used in this example

8

Int. DB

Address

290

The integer data will copied to the database starting at

word-address 290 (from 290 to 292)

9

Word Count

3

The command returns 3 words of integer data

10

Swap Code

3

The bytes in each returned integer data will be

swapped

11

Use Long

1

This command executes using Long Address

12

Enable

Address

-1

This command does not use this feature

13

DB Done

Address

-1

This command does not use this feature

14

DB Write

Address

-1

This parameter is ignored since no data is sent to the

HART device (this is a read command)

15

DB Swap

Code

3

This parameter is ignored since no data is sent to the

HART device (this is a read command)

16

Byte Count

0

This parameter is ignored since no data is sent to the

HART device (this is a read command)

17

Fixed Data

This command does not use this feature

So these values could be entered in the configuration file as described below:

In this example, the user should verify that the command result is located inside

the Read Data area, in order to have the data copied to the PLC processor

(through the backplane). The following backplane configuration could be used for

this example:

Read Register Start : 0 #Starting DB address where read by processor
Read Register Count : 300 #Number of regs for processor to read
Write Register Start: 300 #Starting DB address where write data placed
Write Register Count: 300 #Number of regs to write to module from processor