Markings – ProSoft Technology MVI69-HART User Manual
Page 4
![background image](https://www.manualsdir.com/files/866096/content/doc004.png)
Markings
Electrical Ratings
Backplane Current Load: 800 mA @ 5.1 Vdc
Power Supply Distance Rating: 2
Operating Temperature: 0°C to 60°C (32°F to 140°F)
Storage Temperature: -40°C to 85°C (-40°F to 185°F)
Relative Humidity: 5% to 95% (with no condensation)
All phase conductor sizes must be at least 1.3 mm(squared) and all earth ground conductors must be at least
4mm(squared).
Label Markings
Class I, Division 2 Groups A, B, C, D
II 3 G
Ex nA IIC X
0°C <= Ta <= +60°C
II - Equipment intended for above ground use (not for use in mines).
3 - Category 3 equipment, investigated for normal operation only.
G - Equipment protected against explosive gasses.
Agency Approvals and Certifications
Agency
Applicable Standard(s)
ATEX
EN 60079-0:2006, EN 60079-15:2005
DNV
DET NORSKE VERITAS Test 2.4
CE
EMC-EN61326-1:2006; EN61000-6-4:2007
CB Safety
CA/10533/CSA, IEC 61010-1 Ed. 2, CB 243333-2056722
(2090408)
GOST-R
EN 61010
ME06