Command Control(Block 9902)
The block 9902 identification code is used by the processor to enable a set of
commands that have their enable code set to 4 or 5 (one shot). The value
referenced by the address associated with the command, Enable DB Address,
will be set to -1 to enable the command for a one-shot (enable code 5) or
continuous (enable code 4) execution. After the command is executed, the
module resets the register to 0 to disable the command for the one-shot mode.
The format for this command block is shown in the following table.
Word Offset in Block
Data Field(s)
Description
0
Block ID
This field contains the value of 9902 identifying the
enable command to the module.
1
Port Number
This is the HART port number (0 to 3) for the
command. Each port has its own command list.
2
Command
count
This field contains the number of commands to enable
in the command list. Valid values for this field are 1 to
60.
3 to 62
Command
Numbers to
enable
These 60 words of data contain the command numbers
in the command list to enable. The value referenced by
the Enable DB address associated with each command
will be set to -1.
63
Spare
Not Used
There is no response to this block by the module.
Command Disable Control Block (Block 9903)
The block 9903 identification code is used by the processor to disable a set of
commands that have an enable code set to 4 or 5 (one shot). The value
referenced by the address associated with the command, Enable DB Address,
will be set to 0 to disable the command. The format for this command block is
shown in the following table.
Word Offset in Block
Data Field(s)
Description
0
Block ID
This field contains the value of 9903 identifying the
enable command to the module.
1
Port Number
This is the HART port number (0 to 3) for the
command. Each port has its own command list.
2
Command
count
This field contains the number of commands to disable
in the command list. Valid values for this field are 1 to
60.
3 to 62
Command
Numbers to
enable
These 60 words of data contain the command numbers
in the command list to disable. The value referenced by
the Enable DB address associated with each command
will be set to 0.
63
Spare
Not Used
There is no response to this block by the module.