ProSoft Technology MVI69-HART User Manual
Page 44
![background image](https://www.manualsdir.com/files/866096/content/doc044.png)
Module Configuration
MVI69-HART ♦ CompactLogix Platform
User Manual
HART Multi-drop Master Communication Module
Page 44 of 169
ProSoft Technology, Inc.
March 29, 2012
2.3.2 Example of HART Command Function 34
The following example shows how to configure a command function 34 (WRITE
DAMPING VALUE) to write a damping values (seconds) to the HART slave
device.
According to the HART specification, this command will write one floating point
variables:
Word
High Byte
Low Byte
0
Floating Point Damping Value (Sec)
1
The HART device should also return the floating point value after it processes the
request:
Word
High Byte
Low Byte
0
Floating Point Damping Value (Sec)
1
The HART device also returns an integer status data:
Word
High Byte
Low Byte
1
STATUS WORD
This command will return the following number of words:
Parameter
Data Type
Direction
Number of
Words
Database Address
(this example)
Damping Value Floating Point Written from MVI to slave
2 (4 bytes)
400 (word address)
or 800 (byte
address)
Damping Value Floating Point Read from slave to MVI
2
240 (word address)
Status Word
Integer
Read from slave to MVI
1
290 (word address)