beautypg.com

ProSoft Technology MVI69-HART User Manual

Page 110

background image

Reference

MVI69-HART ♦ CompactLogix Platform

User Manual

HART Multi-drop Master Communication Module

Page 110 of 169

ProSoft Technology, Inc.

March 29, 2012

Offset

Content

Description

19

Device Status (bit mapped)

Each bit in this word corresponds to a slave address
on the network starting at bit 1 for slave address 1. Bit

0 is not used. If the bit is set, the slave is in error. If

the bit is clear (0), the slave is not in error.

20

Device Poll List (bit mapped) Each bit in this word corresponds to a slave address

on the network starting at bit 1 for slave address 1. Bit

0 is not used. If the bit is set, the slave is in the poll

list. If the bit is clear (0), the slave is not in the poll list.

21

Device With Long Address

(bit mapped)

Each bit in this word corresponds to a slave address

on the network starting at bit 1 for slave address 1. Bit
0 is not used. If the bit is set, the slave uses the long

address. If the bit is clear (0), the slave does not use

the long address.

22

Current Command

This field contains the index of the current command

to execute.

23

Command Request Count

This field contains the total number of request

messages issued on the port.

24

Command Response Count This field contains the total number of response

messages received from devices on the network.

25

Configuration Error Word

Configuration error word (see table)

26

Current Error Code

Current error code for port

27

Last Error Code

Last error code reported for port

28

Channel 2 State

Channel 2 state machine value (used for debugging)
0 Polling
1 Config
2 Data Poll
3 User Poll
4 Wait Unique ID

29

Comm State

Channel 2 communication state machine value (used

for debugging)
0 Startup
1 Idle
2 Transmit Pending
3 Transmit
4 Receive
5 Post Transmit
6 Idle, Waiting

30

Device Status (bit mapped)

Each bit in this word corresponds to a slave address
on the network starting at bit 1 for slave address 1. Bit

0 is not used. If the bit is set, the slave is in error. If

the bit is clear (0), the slave is not in error.

31

Device Poll List (bit mapped) Each bit in this word corresponds to a slave address

on the network starting at bit 1 for slave address 1. Bit
0 is not used. If the bit is set, the slave is in the poll

list. If the bit is clear (0), the slave is not in the poll list.

32

Device With Long Address

(bit mapped)

Each bit in this word corresponds to a slave address
on the network starting at bit 1 for slave address 1. Bit

0 is not used. If the bit is set, the slave uses the long

address. If the bit is clear (0), the slave does not use

the long address.