ProSoft Technology MVI69-DFNT User Manual
Page 56

Ladder Logic
MVI69-DFNT ♦ CompactLogix or MicroLogix Platform
User Manual
EtherNet/IP Client/Server Communication Module
Page 56 of 167
ProSoft Technology, Inc.
May 14, 2014
4 Enter the values shown in the following illustration to define the module
correctly for the MicroLogix processor, and then click OK
to save your
configuration.
The Input Words and Output Words parameters will depend on the Block
Transfer Size parameter you specify in the configuration file. Use the values
from the following table.
Block Transfer Size
Input Words
Output Words
60
62
61
120
122
121
240
242
241
5 Click OK
to continue.
6 After completing the module setup, the I/O Configuration dialog box will
display the module's presence.
The last step is to add the ladder logic. If you are using the example ladder logic,
adjust the ladder to fit your application.
Download the new application to the controller. If you encounter errors when you
attempt to run the program, refer to Diagnostics and Troubleshooting (page 57)
for information on how to connect to the module's Config/Debug port to use its
troubleshooting features.