ProSoft Technology MVI69-DFNT User Manual
Page 129

MVI69-DFNT ♦ CompactLogix or MicroLogix Platform
Reference
EtherNet/IP Client/Server Communication Module
User Manual
ProSoft Technology, Inc.
Page 129 of 167
May 14, 2014
The T
ARGET
D
EVICE
D
ATA
T
ABLE
A
DDRESS
must be set to a valid file element
(such as, N11:0) for SLC and PLC5 messages. The M
ULTI
H
OP
option must be
set to Y
ES
.
The M
ULTI
H
OP
tab portion of the dialog box must be completed as
displayed in the following window:
Set the IP address value to the module’s Ethernet IP address. You must press
the "Insert" key to add the second line for ControlLogix Backplane and set the
slot number to zero.
SLC5/05 Read Commands
Read commands transfer data to the SLC processor from the DFNT module. An
example rung used to execute a read command is shown in the following
diagram: